GUO HONGWEI, WANG YU, GAO WENXUE, et al. Performance Evaluation of Solar-air Source Heat Pump Hot Water System in Different Climatic Zones. [J]. Journal of refrigeration, 2019, 40(4).
GUO HONGWEI, WANG YU, GAO WENXUE, et al. Performance Evaluation of Solar-air Source Heat Pump Hot Water System in Different Climatic Zones. [J]. Journal of refrigeration, 2019, 40(4). DOI: 10.3969/j.issn.0253-4339.2019.04.045.
To obtain the applicability and operation superiority of the solar-air source heat pump hot water system in different regions
the operation performance and energy efficiency coefficient of the air source heat pump unit and solar collector unit were tested through experiments under typical conditions. Tianjin
Shanghai
Guangzhou
and Kunming were selected for cold
hot-summer and cold-winter
hot-summer and warm-winter
and temperate regions
respectively. With the consideration of Chinese habits on domestic hot water
the performance of the heat pump system was analyzed in different areas for a typical family with 3~5 persons. The annual performance factor (APF) of a hot water system in different regions is calculated based on the weighted annual meteorological data of different cities. It is concluded that the APF of the hot water system is 3.03
3.34
3.79
and 3.28 in cold
hot-summer and cold-winter
hot-summer and warm-winter
and temperate regions
respectively
and the annual contribution rate of solar energy in the four regions is 29.82%
32.07%
29.58%
and 38.62%
respectively. The APF of the combination system can reach 3.67
4.06
4.39
and 4.45
respectively.
关键词
空气源热泵太阳能集热器热水系统年能效系数不同气候区
Keywords
air source heat pumpsolar collectorhot water systemAPFdifferent climate zones