双蒸发温度的温湿分控空调机组实验研究
陈剑波, 信文普, 顾娟
0
(上海理工大学环境与建筑学院)
摘要:
针对传统热湿联合处理中存在的能源浪费、热湿平衡不匹配等问题,本文利用EnergyPlus软件对上海市某住宅建筑进行全年逐时负荷模拟。根据模拟结果将温湿度独立控制技术与双蒸发温度压缩机结合在一起,搭建了基于双蒸发温度的温湿分控空调机组实验台。在进行相关理论计算的基础上对其在全年工况下运行特性进行实验研究。结果表明:将具有双蒸发温度压 缩机的空调机组用于温湿分控空调系统是可行的,机组运行可靠且满足设计要求。夏季设计工况下该机组压缩机能效比为3.5,比同冷量常规空调变频压缩机的能效比3.04提高了14.8%。同时,冬季设计工况下该机组压缩机能效比为4.3,相对于同冷量常规空调变频压缩机而言,双蒸发温度的温湿分控空调机组节能性显著。
关键词:  空调机组  温湿度独立控制  双蒸发温度  能效比
DOI:
投稿时间:2019-12-16  修订日期:2020-06-20  
基金项目:
Experiment on Temperature- and Humidity-Controlled Air Conditioner with Dual Evaporation Temperature
Chen Jianbo, Xin Wenpu, Gu Juan
(School of Environment and Architecture, University of Shanghai for Science and Technology)
Abstract:
To address the problems of energy waste and imbalance between heat and humidity in traditional combined heat and moisture treatment, the annual hourly energy consumption of a residential building in Shanghai was simulated by EnergyPlus software in this study. According to the simulation results, the independent temperature and humidity control technique was combined with dual evaporative temperature compressor, and a temperature- and humidity-controlled air conditioner test bed was established based on dual evaporation temperature. Relevant theoretical calculations were performed, and the operational characteristics of the air conditioner under whole-year operation conditions were experimentally investigated. The results show that it is feasible to use an air-conditioning unit with a double evaporative temperature compressor in an air-conditioning system with separately controlled temperature and humidity, which meets the design requirements and has obvious energy efficiency. In summer, the energy efficiency ratio of the compressor is 3.5, which is 14.8% higher than that of the inverter compressor of conventional air conditioning with the same cooling capacity (3.04). At the same time, the energy efficiency ratio of the unit compressor under the design conditions in winter is 4.3. Compared with the inverter compressor of conventional air conditioning with the same cooling capacity, the air conditioner with dual evaporation temperature shows remarkable energy savings.
Key words:  air conditioner unit  independent temperature and humidity control  dual evaporation temperature  energy efficiency ratio