翁文兵, 罗诗雨, 白俊武. 换热器面积对双蒸发温度空调系统性能影响的模拟研究[J]. 制冷学报, 2024,45(3):89-96.
WENG WENBING, LUO SHIYU, BAI JUNWU. Simulation Study on the Effect of Heat Exchanger Area on the Performance of Dual Evaporatingon Temperature Air Conditioning System. [J]. Journal of refrigeration, 2024, 45(3): 89-96.
翁文兵, 罗诗雨, 白俊武. 换热器面积对双蒸发温度空调系统性能影响的模拟研究[J]. 制冷学报, 2024,45(3):89-96. DOI: 10.3969/j.issn.0253-4339.2024.03.089.
WENG WENBING, LUO SHIYU, BAI JUNWU. Simulation Study on the Effect of Heat Exchanger Area on the Performance of Dual Evaporatingon Temperature Air Conditioning System. [J]. Journal of refrigeration, 2024, 45(3): 89-96. DOI: 10.3969/j.issn.0253-4339.2024.03.089.
建立了双蒸发温度空调系统仿真模型来研究改变换热器面积对系统性能的影响。搭建了双蒸发温度空调系统实验台,在实验工况下改变压缩机频率(30~120 Hz)和送风量(400~1000 m3/h),得到空调机组总制冷量Qc、总显热制冷量Qs和显热比SHR,验证了所建模型精度。在模型中改变换热器面积(48盘管、60盘管、72盘管)进行系统运行调节范围的研究。结果表明:随着换热器面积的增加,系统Qc、Qs和SHR的调节范围在整体扩大,最大增幅分别为5.0%、13.8%、11.8%。当送风量为1 000 m3/h,压缩机频率为30 Hz,换热器面积从48盘管增至60盘管、72盘管时,Qs的增幅分别为9.8%和13.8%,表明换热器面积增至60盘管时Qs增长效果显著,再增加换热器面积,Qs虽有所增大但增幅放缓。最后提出一种以所需制冷量为目标,依据环境温湿度调节范围设计换热器面积的方法。
In response to the issue of heat exchanger design in a dual evaporating temperature air conditioning system
in this study
a simulation model is established for a dual evaporating temperature air conditioning system to evaluate the impact of the heat exchanger area on the system performance. A dual evaporating temperature air-conditioning system experimental platform is built
and the compressor frequency (30–120 Hz) and supply air volumetric flow rate (400–1000 m3/h) under experimental conditions are used to obtain the cooling capacity Qc
sensible heat cooling capacity Qs
and sensible heat ratio (SHR) of the air-conditioning unit. These performance metrics are used to verify the accuracy of the established model. The range of the system operation adjustment is studied by changing the heat exchanger area (48
60
and 72 coils) in the model. The results show that with an increase in the heat exchanger area
the adjustment ranges of systems Qc
Qs
and SHR expand generally
with maximum increases of 5.0%
13.8%
and 11.8%
respectively. When the heat exchange area increased from 48 to 60 coils and 72 coils
at an air supply volumetric flow rate of 1000 m3/h and the compressor frequency of 30 Hz
the increase in Qs was 9.8% and 13.8%
respectively
indicating that when the heat exchange area increased to 60 coils
the increase in Qs was obvious. When the heat exchange area was further increased
although Qs increased
the growth rate decreased. Finally
a method was proposed to design the heat exchanger area according to the ambient temperature and humidity adjustment range
with the required cooling capacity as the target.
双蒸发温度显热比制冷量温湿度独立控制
dual evaporating temperaturesensible heat ratiorefrigeration capacityindependent temperature and humidity control