陶奕玮, 刘剑, 李明霞, 等. 冷水(热泵)机组能效测试方法及能效限定值的对比研究[J]. 制冷学报, 2024,45(2).
TAO YIWEI, LIU JIAN, LI MINGXIA, et al. Comparative Study of Energy Efficiency Test Methods and Energy Efficiency Limit Values of Water Chiller (Heat Pump) Units. [J]. Journal of refrigeration, 2024, 45(2).
陶奕玮, 刘剑, 李明霞, 等. 冷水(热泵)机组能效测试方法及能效限定值的对比研究[J]. 制冷学报, 2024,45(2). DOI: 10.3969/j.issn.0253-4339.2024.02.030.
TAO YIWEI, LIU JIAN, LI MINGXIA, et al. Comparative Study of Energy Efficiency Test Methods and Energy Efficiency Limit Values of Water Chiller (Heat Pump) Units. [J]. Journal of refrigeration, 2024, 45(2). DOI: 10.3969/j.issn.0253-4339.2024.02.030.
冷水(热泵)机组作为集中空调系统的主要耗能设备,行业整体机组能效的提高会对按期实现“双碳”目标具有重大促进作用。GB/T 18430作为冷热水机组的基础性标准,修订工作已接近尾声,与之配套的能效标准GB19577?—2015也需要进行相应的修订升级。对GB/T 18430中对舒适型冷水(热泵)机组的考核方法与对应美国和欧洲的进行了对比分析,构建了一个水冷式冷水(热泵)机组的理论模型,从而将中国、美国和欧洲能效标准中规定的限定值水平折算为同一个指标下进行对比。对比发现,我国目前水冷式机组的IPLV入门限定值分别提升5.4%和25.2%后可以达到美国能效标准A路径和B路径能效水平,提升13.4%后可与欧洲能效标准水平持平;风冷式机组能效限定值在数值上增加25.4%后可与欧洲能效标准基本持平。本文的工作为后续能效标准GB19577—2015的修订提供了参考依据。
As the main energy-consuming equipment of the centralized air-conditioning system
the improvement of the energy efficiency of water chiller (heat pump) units has a significant role in promoting the realization of the "dual carbon" target. GB/T 18430
as a basic standard for plumbing units
is nearing the end of its revision
and the accompanying energy efficiency standards GB19577–2015 need to be revised and upgraded accordingly. In this study
the assessment method of comfort-type water chiller (heat pump) units in GB/T 18430 is analyzed and compared with those of the corresponding U.S. and European standards. A theoretical model of water-cooled water chiller (heat pump) units is constructed such that the limited value levels specified in the energy efficiency standards of China
the U.S.
and Europe are converted into the same index for comparison. The IPLV entry limit values of China's water-cooled units
after increases of 5.4% and 25.2%
can match the energy efficiency levels of Path A and Path B of the American standard
respectively
and align with the European standards after a 13.4% increase; the energy efficiency limit values of air-cooled units can be basically on par with the European energy efficiency standards after increasing by 25.4%. This work provides a reference for the subsequent revision of the energy efficiency standard GB19577—2015.
冷水(热泵)机组IPLV测试方法对比能效限值
chiller(heat pump)integrated part load valuecomparison of test methodsenergy efficiency limit value