SUN XIAOQING, HAN ZONGWEI, YANG ZIWEI, et al. Analysis of Cooling Capacity of Backplane Air-cooled Rack. [J]. Journal of refrigeration, 2023, 44(4). DOI: 10.3969/j.issn.0253-4339.2023.04.159.
Backplane air conditioner cooling solves the heat dissipation problem inside a rack
which can reduce the waste of cooling capacity and significantly improve refrigeration efficiency. To explore the cooling capacity of a backplane air-cooled rack under different working conditions
a rack model was established using CFD simulation software to simulate the thermal environment of the rack. The results showed that the air distribution inside the rack was good
and there was no mixing of cold and hot air. The server temperature decreased with an increase in the circulating air volumetric flow rate
and the decreasing trend saturated at higher flow rates. As the inlet air temperature increased
the server temperature increased linearly. When the inlet air temperature was 18
20
22
24
and 26 °C
by changing the total circulating air volumetric flow rate changed within the range of 2 400–3 200 m3/h
the maximum load power range of a 42U rack was 11.7–15.0 kW
11.2–14.5 kW
10.8–14.0 kW
10.3–13.4 kW and 9.8–12.7 kW.
关键词
数据中心背板式机柜冷却能力模拟研究
Keywords
data centerbackplane rackcooling capacitysimulation study