YU YINGRUI, WEI JUAN, LI WEIZHAO, et al. Experimental Study on Performance of Zero-emission Heat Pump System for Exhaust Gas after Drying Process in Pharmaceutical Industry. [J]. Journal of refrigeration, 2023, 44(1).
YU YINGRUI, WEI JUAN, LI WEIZHAO, et al. Experimental Study on Performance of Zero-emission Heat Pump System for Exhaust Gas after Drying Process in Pharmaceutical Industry. [J]. Journal of refrigeration, 2023, 44(1). DOI: 10.3969/j.issn.0253-4339.2023.01.043.
This study develops a zero-emission heat pump system consists of heat pipes
water coils
and heat pumps for exhaust gas to mitigate the incomplete treatment
disgusting smell
and unrecoverable heat of exhaust gas after the drying process in the pharmaceutical industry. The quality of gas recycling and reuse is guaranteed by closed-loop dehumidification
waste gas treatment
and heating
thereby achieving near-zero emissions and recovery of waste heat. The experimental results of the system performance show that when the average temperature of the supply air is 65.1 °C
the relative humidity of the supply air is 21.1%
the air volumetric flow rate is 12 000 m3/h
the coefficient of performance of the heat pump unit is 4.7
and the specific moisture extraction rate of the system is 8.5 kg/(kW?h). The composition of the circulating gas shows that 73.2% of the volatile organic compounds are absorbed
and no non-condensable
flammable
or explosive gases are accumulated in the system during each production period.
关键词
热泵热管干燥废气处理闭式循环
Keywords
heat pumpheat pipedryingwaste gas treatmentclosed circulation