金梧凤, 薛探栋, 袁小勇, 等. R32制冷剂泄漏位置对浓度分布与室内安全性的实验研究[J]. 制冷学报, 2022,43(5).
JIN WUFENG, XUE TANDONG, YUAN XIAOYONG, et al. Experimental Study on Concentration Distribution and Indoor Safety of R32 Refrigerant Leakage Location. [J]. Journal of refrigeration, 2022, 43(5).
金梧凤, 薛探栋, 袁小勇, 等. R32制冷剂泄漏位置对浓度分布与室内安全性的实验研究[J]. 制冷学报, 2022,43(5). DOI: 10.3969/j.issn.0253-4339.2022.05.114.
JIN WUFENG, XUE TANDONG, YUAN XIAOYONG, et al. Experimental Study on Concentration Distribution and Indoor Safety of R32 Refrigerant Leakage Location. [J]. Journal of refrigeration, 2022, 43(5). DOI: 10.3969/j.issn.0253-4339.2022.05.114.
本文通过实验研究的方法,对比分析了R32制冷剂在泄漏量为3.6 kg,不同泄漏位置时,R32气体在室内不同平面的浓度扩散规律,并通过典型平面首次达到可燃下限(LFL)的时间和可燃风险时间来分析室内的安全性影响。结果表明:随着泄漏位置高度的增加,制冷剂浓度扩散速率在沿高度方向上逐渐趋于一致,浓度上升速率和浓度下降速率分别保持在约0.5%/min和0.06%/min。当制冷剂气体从房间上部水平方向泄漏改变为垂直向下泄漏时,泄漏口附近平面处最大浓度及浓度扩散速率均减小约50%,可燃危险时间减少了约78%;房间下部的的可燃危险时间随泄漏位置高度的升高而逐渐增大。当泄漏位置位于房间上部和顶部时,房间底部区域最先达到LFL值,其余位置处泄漏口附近平面处最先达到LFL值。
In this study
an experiment was conducted to compare and analyze the concentration diffusion law of R32 gas in different planes ofthe testedroom following leakage from different positions of 3.6 kg R32 refrigerant. The safety impact in the room when the lower flammable limit (LFL) was reached for the first time in typical planes was analyzed along with the flammable risk time. The results showed that when the height of the leak position increased
the concentration diffusion rate of refrigerant gradually converged along the height direction. The concentration increase and decrease rates remained at approximately 0.5%/min and 0.06%/min
respectively. When the refrigerant gas leaked horizontally from the upper part of the room
the maximum concentration and concentration diffusion rate at the plane near the leak was reduced by approximately 50%
with the flammable risk time reduced by approximately 78%. The flammable risk time at the lower part of the room increased gradually with the height of the leak location. When the leak was in the upper part of the room
the LFL value was reached first at the bottom of the room and then in the planesthat are close to the leaking position.
可燃制冷剂泄漏浓度分布可燃风险时间安全性评价
leakage of combustible refrigerantconcentration distributionflammable risk timesafety evaluation