Zhang Longai, Wang Chuanhua, Qu Qinggao, et al. Design and Experimental Research on Dual Cold Sources Dehumidification System with Temperature Adjustment and Heat Recovery[J]. Journal of refrigeration, 2021, 42(4).
Zhang Longai, Wang Chuanhua, Qu Qinggao, et al. Design and Experimental Research on Dual Cold Sources Dehumidification System with Temperature Adjustment and Heat Recovery[J]. Journal of refrigeration, 2021, 42(4). DOI: 10.3969/j.issn.0253-4339.2021.04.083.
In a traditional temperature and humidity independent control system
low temperatures and a high relative humidity of fresh air happens when condensation dehumidification is used for fresh air treatment. In this study
a temperature-adjustable energy-saving dehumidification system with double cold sources was proposed to solve these problems. Theoretical analysis and experimental verification were conducted to study the factors affecting the supply air status
including compressor frequency
cooling coil water flow
and fresh air volume. Control devices were then developed for the supply air status in accordance with its variation. The results show that the system has a satisfactory adjustability of the comfortable supply air. Under standard conditions
the supply air temperature can be as high as 25.0 ℃. Compared with conventional dehumidification
the efficiency improvement of this new system is up to 93.6%.