Gao Feng, Wang Yu, Li Yanju, et al. Experimental Study on Heating Performance of Air-source Heat Pump Coupled with a New Type Radiant Floor[J]. Journal of refrigeration, 2021, 42(4).
Gao Feng, Wang Yu, Li Yanju, et al. Experimental Study on Heating Performance of Air-source Heat Pump Coupled with a New Type Radiant Floor[J]. Journal of refrigeration, 2021, 42(4). DOI: 10.3969/j.issn.0253-4339.2021.04.065.
In order to analyze the actual heating effect and operation performance of a new type of radiant floor heating system coupled with air-source heat pump applied in the northern cold area
a 76-day field test was conducted in an office building for the management of residential area in Tianjin. During the test period
the average temperature of indoor working area was 18.4~21.8 ℃
and the average indoor surface temperature was 22.5~29.1 ℃. More than 90% of indoor LPD1 and LPD2 were in grade I index. The average daily heating capacity and power are 1.5~6.9 kW and 0.6~3.2 kW
respectively; the daily average power consumption is 0.79 kW?h/m2
and the daily average COP is 1.43~3.54. When the temperature difference between the floor surface and the the office area is within 5 ℃
the heat dissipation can still reach 50–100 W/m2. In the coldest test days
the outdoor temperature is -10.1~2.1 ℃
the average temperature in the working area of three indoor test positions is 21.4 ℃
the lowest indoor instantaneous temperature is 16.4 ℃
LPD1 and LPD2 are all in the standard range of grade I and II
which ensures the heating quality. The range of the heating capacity and power of the system is 6.1~10.9 kW and 2.9~3.3 kW