ZHANG YUHANG, SUN BO, ZHANG XIAOSONG, et al. Design and Performance Analysis under Winter Condition of a Residential Ground-source Heat Pump System. [J]. Journal of refrigeration, 2020, 41(5).
ZHANG YUHANG, SUN BO, ZHANG XIAOSONG, et al. Design and Performance Analysis under Winter Condition of a Residential Ground-source Heat Pump System. [J]. Journal of refrigeration, 2020, 41(5). DOI: 10.3969/j.issn.0253-4339.2020.05.089.
A ground source heat-pump system for a residential community in Yangzhou was designed and tested under winter conditions. The operating performance was evaluated and ground thermal imbalance problem was also analyzed based on the annual energy consumption of the air conditioning system of the community. The results showed that the ground source heat pump system requires 1087 vertical wells for heat transfer
the water temperature at the outlet of the buried pipe was 8.5–9.0 ℃
the coefficient of performance (COP) of heat pump unit was 3.67–4.17
and the system COP was 2.66. Based on the test data
it is concluded that the main reason for the low system COP is that the system operates at low temperature differences between inlet and outlet and large flow rate at low partial load rates
and thereby resulting in higher pump power consumption. Conversely
based on the combined annual air-conditioning energy consumption data of the community
it is concluded that the system's heat extraction in winter and the heat release in summer are unbalanced
and thereby resulting in a decrease in soil temperature.
关键词
地源热泵系统设计性能分析热平衡住宅小区
Keywords
ground-source heat pumpsystem designperformance analysisthermal imbalanceresidential community