SHAO YUEYUE, MA GUOYUAN, WANG YUEYUE, et al. Experimental Study on Multi-connected Heat Pump / Heat Pipe Heating Device. [J]. Journal of refrigeration, 2020, 41(4).
SHAO YUEYUE, MA GUOYUAN, WANG YUEYUE, et al. Experimental Study on Multi-connected Heat Pump / Heat Pipe Heating Device. [J]. Journal of refrigeration, 2020, 41(4). DOI: 10.3969/j.issn.0253-4339.2020.04.032.
A heating cycle mode of heat pump drive multi-connected heat pipe is proposed. The feature of this method is that the air source heat pump is used to drive tandem heat pipe radiator for heating directly. In order to verify the feasibility of this heating method
an experimental platform was built based on a 2.5 kW compressor and 9 heat pipe radiators
and the device was tested under different working conditions. The test results show that the new heating device has a faster starting speed
when the outdoor temperature is -10 °C and the system runs for 36 minutes
the surface temperature of the heat pipe radiator can reach 45 °C. Heat is evenly distributed at the end of the heat pipe radiator. Except for 1# and 9# radiators
which have over-cooling and over-heating
the temperature difference between the other radiators is approximately 1 °C. At the same time
the system has a small heat transfer temperature difference and can operate normally under defrost conditions.