LUO LIANG, HUANG ZHIJIA, WANG XIAOYU, et al. Performance Analysis and Optimization of Heat Pump Driven Liquid Desiccant Fresh Air System. [J]. Journal of refrigeration, 2020, 41(2).
LUO LIANG, HUANG ZHIJIA, WANG XIAOYU, et al. Performance Analysis and Optimization of Heat Pump Driven Liquid Desiccant Fresh Air System. [J]. Journal of refrigeration, 2020, 41(2). DOI: 10.3969/j.issn.0253-4339.2020.02.123.
A mathematical model of heat pump driven liquid desiccant (HPLD) fresh air system was established to investigate the system’s performance under different fresh air parameters. The results indicated that the average decline rate of the system’s coefficient of performance (COP) was 0.9% when the fresh air temperature increased by 1 ℃
while the average decline rate of COP was 3.6% when the fresh air moisture content increased by 1 g/(kg·dry air). The increase in air moisture content caused a significant reduction in COP
whereas the HPLD system had poor adaptability to the changes in fresh air humidity. In order to expand the range of the HPLD system’s adaptation
a dehumidification system combined with HPLD and cooling dehumidification was proposed. Taking the COP of the combined dehumidification system as the evaluation index
the optimal state of the fresh air parameters between HPLD and cooling dehumidification s was temperature 21 ℃ and moisture content 14.1 g/(kg·dry air). Under typical summer conditions
the COP of the combined dehumidification system was 5.4
which was 87.5% higher than that of a single HPLD system. Finally
an experimental prototype was built according to the design parameters
and simulation results were verified.
关键词
新风除湿系统参数优化溶液除湿性能系数
Keywords
fresh air dehumidification systemparameter optimizationliquid desiccantcoefficient of performance