LI CUICUI, ZHOU FENG, JIN YING, et al. Cooling Loss Characteristics of Working Fluid Pump for Pump-driven Two-phase Circulation Loop. [J]. Journal of refrigeration, 2020, 41(2).
LI CUICUI, ZHOU FENG, JIN YING, et al. Cooling Loss Characteristics of Working Fluid Pump for Pump-driven Two-phase Circulation Loop. [J]. Journal of refrigeration, 2020, 41(2). DOI: 10.3969/j.issn.0253-4339.2020.02.001.
A pump-driven two-phase circulation loop system was built for data center cooling in order to make full use of the ambient energy. In this study
the cooling loss characteristic of working fluid pump was investigated by changing the system temperature difference
pump frequency
heat exchange area
temperature of the high and low-temperature water jacket. The results showed that the cooling loss rate would be minimum at a temperature difference of 16 ℃
frequency of 15 Hz
and a large heat exchange area when the temperature of high-temperature water jacket was kept constant. When the temperature of low-temperature water jacket was kept constant
the cooling loss rate with five evaporators and five condensers under different temperatures was the smallest and less than 3.20%. The higher the temperature of high- temperature water jacket
the lower the cooling loss rate. When the temperature of high-temperature water jacket was 26 ℃
the cooling loss rate was the lowest and did not exceed 2.82%.
关键词
数据中心自然冷却泵驱动回路制冷量冷损率
Keywords
data centerfree coolingpump-driven loopcooling capacitycooling loss rate