Qiu Junjun, Zhang Xiaosong, Li Weihao. Experimental Research on a Frost-free Air Source Heat Pump[J]. Journal of refrigeration, 2019, 40(5). DOI: 10.3969/j.issn.0253-4339.2019.05.026.
A novel air source heat pump systemthat operates efficiently during winter and improvesits performance during summer has been proposed. Based on the experimental results
the regeneration mode and regression analysis of the experimental data were obtained. The relative error of the two formulaswas relatively low
which exhibited a high degree of fitting. The average relative error of regeneration quantity and regeneration efficiency was 0.31% and 0.56%
respectively. Moreover
a correlation analysis was conducted to determine the effects of air volume flow rate
solution temperature
solution volume flow rate
and solution mass fraction on the regeneration performance of the system. The corresponding results demonstrated an increase in the regeneration rate with an increase in the outdoor air flow rate
solution temperature
and solution volume flow rate
and a decrease in the solution mass fraction. In addition
the regeneration efficiency increased by 26.00% and 13.63% with a decrease in the air volume flow rate andan increasein the solution volume flow rate
respectively. Within the scope of this study
regeneration rate demonstrated an increment of 26.30% with an increase in the solution volume flow rateand a decrement of 6.10% with an increase in solution mass fraction
respectively
whereas the solution temperature and mass fraction were found to have slight influence on it.