Liu Shengyao, Li Ying, Huang Caifeng, et al. The Design of Condensate Measurement for Balanced Ambient Room-type Calorimeter[J]. Journal of refrigeration, 2014, 35(2).
Liu Shengyao, Li Ying, Huang Caifeng, et al. The Design of Condensate Measurement for Balanced Ambient Room-type Calorimeter[J]. Journal of refrigeration, 2014, 35(2). DOI: 10.3969/j.issn.0253-4339.2014.02.106.
During the cooling capacity measurement of small and medium size air conditioner
the indoor cooling capacity calculation formula of room-type calorimeter didn’t take the dehumidification of air handling cabinet into consideration. In order to eliminate the impact of this influence on the test results
the mass weighing method was proposed to measure the humidification water of inner and outer chamber of the calorimeter
as well as the condensate water of air conditioner under test respectively. By analyzing the two sets of test results of five test units which were tested by means of room-type calorimeter based on the mass weighing method: It turns out that
when the rated cooling capacity of the air conditioner under test is smaller than the input power of the test chamber
the test error is increased by the air handling cabinet’s dehumidification amount
and the test error arises with the decrease of cooling capacity of air conditioner. The indoor cooling capacity calculation formula is modified to improve its accuracy according to the test results.