Han Xing, Fan Wei, Chen Jianbo, et al. Study of the Frosting Factor Based on Finned-tube Heat Exchanger of Air-source Heat Pump[J]. Journal of refrigeration, 2014, 35(1).
Han Xing, Fan Wei, Chen Jianbo, et al. Study of the Frosting Factor Based on Finned-tube Heat Exchanger of Air-source Heat Pump[J]. Journal of refrigeration, 2014, 35(1). DOI: 10.3969/j.issn.0253-4339.2014.01.025.
The frost on the heat exchanger of air-source heat pump has a great influence on the operating performance. The frosting experiment based on a cascade type air-source heat pump water heater is carried out in the enthalpy-difference chamber in this paper
and the outdoor evaporator of the unit is a finned-tube heat exchanger. The experiment is conducted under the conditions that the outdoor temperature is from -18℃ to 6℃ and outdoor relative humidity is from 70% to 90%. Experimental results show that: First of all
the amount of frosting almost changes linearly with the frosting time which is of maximum in the outdoor temperature range of -3~3℃
and the lower outdoor temperature
the more frosting amount; Secondly
the outdoor relative humidity has a great influence on the quantity of frost
and the more humidity
the more frosting quantity; Finally
the frosting factor is proposed based on the relationships of the area and form of evaporator coil
the time of frosting
the difference of the dew point temperature and the temperature on the evaporator coil and the frosting quantity
and is from 6.51 to 10.31kg/(m2?℃?min) with the average value 8.58×10-4 kg/(m2?℃?min).