Anti-condensation Characteristics of High Permeability Films for Radiation Air Conditioning in Typical Urban Indoor Environments of Different Climate Zones
QU JINGWEI, MA JIANCHAO, ZHENG XIAOHONG, et al. Anti-condensation Characteristics of High Permeability Films for Radiation Air Conditioning in Typical Urban Indoor Environments of Different Climate Zones. [J]. Journal of refrigeration, 2024, 45(5): 90-97.
QU JINGWEI, MA JIANCHAO, ZHENG XIAOHONG, et al. Anti-condensation Characteristics of High Permeability Films for Radiation Air Conditioning in Typical Urban Indoor Environments of Different Climate Zones. [J]. Journal of refrigeration, 2024, 45(5): 90-97. DOI: 10.12465/j.issn.0253-4339.2024.05.090.
Radiant cooling air conditioning systems offer energy savings and thermal comfort; however
the dew problem limits their application and popularization. In this study
a method of applying an infrared high-permeability film to a cold plate was proposed to increase the temperature of the contact surface between the infrared high-permeability film and indoor air while ensuring the radiation cooling capacity of the air conditioning system. This reduces the risk of condensation. A heat transfer model of an infrared transmitting film for radiation refrigeration was constructed
and the influence of the infrared transmittance of the highly permeable film on dew point temperature and radiant cooling capacity was calculated. In addition
the minimum transmittance and corresponding maximum cooling capacity of natural ventilation for preventing condensation in typical cities of different climate zones were predicted
and the effect of the infrared transmittance of the high permeability film on human thermal comfort was evaluated. The results show that the radiant heat transfer model can accurately predict the heat transfer process at the membrane surface. Under the premise of ensuring radiation cooling capacity
the transmission film can increase the dew point temperature by 4 ℃-17 ℃. The minimum transmittance required by different cities vary
with Hohhot and Chongqing having the lowest and highest rates of 0.4 and 0.95
respectively. Infrared transmission films can be used as a novel method to prevent condensation on the cold walls of radiant air conditioning systems. This study thus provides a reference for the design and selection of transmission films.
关键词
辐射空调防结露制冷量高透膜
Keywords
radiant air conditioninganticondensationrefrigerating capacityhigh permeability film