王馨翊,王露,陈晓轩等.数据中心高密度机柜的风冷系统及其散热能力分析[J].制冷学报,2026,47(01):51-58.
Wang Xinyi Wang Lu Chen Xiaoxuan Li Hongrui Li Zhen.Analysis of Air-Cooling System and Heat-Dissipation Capacity for High-Density Cabinets in Data Centers[J].Journal of Refrigeration,2026,47(01):51-58.
王馨翊,王露,陈晓轩等.数据中心高密度机柜的风冷系统及其散热能力分析[J].制冷学报,2026,47(01):51-58. DOI: 10.12465/issn.0253-4339.20250702002. CSTR: XXXXX.XX.XXX.20250702002.
Wang Xinyi Wang Lu Chen Xiaoxuan Li Hongrui Li Zhen.Analysis of Air-Cooling System and Heat-Dissipation Capacity for High-Density Cabinets in Data Centers[J].Journal of Refrigeration,2026,47(01):51-58. DOI: 10.12465/issn.0253-4339.20250702002. CSTR: XXXXX.XX.XXX.20250702002.
随着信息技术的飞速发展和智能算力的广泛应用,单机柜的功率密度不断攀升。这种高功率密度配置在显著提升计算能力的同时,也带来了严峻的散热挑战。针对当前仍以风冷技术为主的数据中心,本文对微通道两相自驱动机柜级风冷系统进行了实验测试,测试结果表明:该系统可实现40 kW的换热能力。将该系统应用于太原某高密度机柜的示范工程中,实测数据显示,在满载条件下,机柜发热功率达到30 kW,本系统能够有效满足其散热需求。并基于实验数据构建了换热过程模型,研究了未来两相自驱机柜级风冷末端在不同外部条件下的换热能力,以期探索风冷系统的换热能力极限。结果显示:在机柜级末端回风温度维持在35 ℃、冷水源温度低至12 ℃、末端迎面风速高达5 m/s的条件下,风冷末端可实现65.2 kW的散热量。通过实验验证和理论分析,可为存量风冷数据中心进一步提升算力提供新的可能性和技术支撑。
With the rapid development of information technology and the wide application of intelligent arithmetic, the power density of a single cabinet continues to increase. Such high-power-density configurations cause severe cooling challenges while significantly increasing computing power. This study tests a two-phase microchannel self-driven cabinet-level air-cooling system for data centers dominated by air-cooling technology. The test results show that the system can achieve a heat-transfer capacity of 40 kW. The system is subsequently applied to a high-density cabinet demonstration project in Taiyuan. The measured data show that when the power of the cabinet reaches 30 kW under full-load conditions, this system can effectively satisfy its heat-dissipation requirements. In addition, this study constructs a heat-transfer model based on experimental data and further explores the heat-transfer capability of two-phase self-driven cabinet-level air-cooled terminals under different external conditions, with the aim of exploring the limits of air-cooling systems. The results show that the air-cooled terminal can realize a heat dissipation of 65.2 kW if the return air temperature of the cabinet-level terminal is maintained at 35 ℃, the temperature of the chilled water source is as low as 12 ℃, and the wind speed on the terminal reaches 5 m/s. Based on experimental validation and theoretical analysis, this study offers new possibilities and technical support for stock air-cooled data centers to further improve their arithmetic power.
景传刚 , 李楠 , 宋晓伟 . 不同功率密度机柜对数据中心的影响分析 [J]. 通信电源技术 , 2019 , 36 ( 10 ): 85 - 88 .
JING Chuangang , LI Nan , SONG Xiaowei . Effect of different power density racks on data center [J]. Telecom Power Technology , 2019 , 36 ( 10 ): 85 - 88 .
陈焕新 , 程亨达 . 数据中心及超算中心冷却技术研究及应用进展 [C]//中国制冷学会. “2022年双碳背景下中国制冷技术研究及应用进展论坛”会议论文集 . 北京 , 2023 : 6 .
CHEN Huanxin , CHENG Hengda . Research and application progress of cooling technologies for data centers and supercomputing centers [C]// Chinese Association of Refrigeration . Proceedings of the 2022 Forum on Research and Application Progress of Refrigeration Technologies under Dual-Carbon Background in China . Beijing , 2023 : 6 .
陈心拓 , 周黎旸 , 张程宾 , 等 . 绿色高能效数据中心散热冷却技术研究现状及发展趋势 [J]. 中国工程科学 , 2022 , 24 ( 4 ): 94 - 104 .
CHEN Xintuo , ZHOU Liyang , ZHANG Chengbin , et al . Research status and future development of cooling technologies for green and energy-efficient data centers [J]. Strategic Study of CAE , 2022 , 24 ( 4 ): 94 - 104 .
孙文帅 . 某数据机房精密空调送回风温度控制方案对比分析 [J]. 洁净与空调技术 , 2025 ( 1 ): 46 - 51 .
SUN Wenshuai . Comparative analysis of the control scheme of supply air temperature and return air temperature for precision air conditioners in a data center module computer room [J]. Contamination Control & Air-Conditioning Technology , 2025 ( 1 ): 46 - 51 .
蒋雅靖 , 刘成 . 列间空调在高密度数据中心应用的数值模拟 [J]. 建筑热能通风空调 , 2012 , 31 ( 6 ): 92 - 95 .
JIANG Yajing , LIU Cheng . Numerical simulation of inter-column air-conditioning in high-density Internet data centre [J]. Building Energy & Environment , 2012 , 31 ( 6 ): 92 - 95 .
田振武 , 张金辉 , 黄翔 , 等 . 数据中心双冷源列间空调系统设计与实测分析 [J]. 制冷与空调(四川) , 2022 , 36 ( 6 ): 850 - 853 .
TIAN Zhenwu , ZHANG Jinhui , HUANG Xiang , et al . Design and measurement analysis of double cooling air conditioning system in data center [J]. Refrigeration & Air Conditioning , 2022 , 36 ( 6 ): 850 - 853 .
孙永才 , 麦新有 . 微通道重力热管背板换热性能试验研究 [J]. 建筑节能(中英文) , 2022 , 50 ( 10 ): 88 - 92 .
SUN Yongcai , MAI Xinyou . Experimental study on heat exchange performance of microchannel gravity heat pipe backplane [J]. Building Energy Efficiency , 2022 , 50 ( 10 ): 88 - 92 .
中国信息通信研究院云计算与大数据研究所 . 算力中心冷板式液冷发展研究报告 [R/OL].( 2024-05-01 ) [ 2025-05-26 ]. https://www.caict.ac.cn/kxyj/qwfb/ztbg/202405/P020240523566116859176.pdf https://www.caict.ac.cn/kxyj/qwfb/ztbg/202405/P020240523566116859176.pdf .
Cloud Computing & Big Data Research Institute of China Academy of Information and Communications Technology . Research report on cold plate liquid cooling development in computing power centers [R/OL].( 2024-05-01 )[ 2025-05-26 ]. https://www.caict.ac.cn/kxyj/qwfb/ztbg/202405/P020240523566116859176.pdf https://www.caict.ac.cn/kxyj/qwfb/ztbg/202405/P020240523566116859176.pdf .
HEYDARI A , GHARAIBEH A R , TRADAT M , et al . Experimental evaluation of direct-to-chip cold plate liquid cooling for high-heat-density data centers [J]. Applied Thermal Engineering , 2024 , 239 : 122122 .
潘永莉 , 王会娟 , 宗皓男 , 等 . 数据中心服务器浸没式液冷技术研究进展 [J]. 润滑油 , 2024 , 39 ( 6 ): 7 - 13 .
PAN Yongli , WANG Huijuan , ZONG Haonan , et al . Research progress on immersion liquid cooling technology for data center servers [J]. Lubricating Oil , 2024 , 39 ( 6 ): 7 - 13 .
蒋绍辉 , 张博博 , 熊滕 , 等 . 数据中心液冷技术的应用研究进展 [J]. 新能源进展 , 2025 , 13 ( 2 ): 204 - 213 .
JIANG Shaohui , ZHANG Bobo , XIONG Teng , et al . Research progress on application of liquid cooling technology in data center [J]. Advances in New and Renewable Energy , 2025 , 13 ( 2 ): 204 - 213 .
陈焕新 , 王宜卿 , 张丽 , 等 . 数据中心发展进展 [J]. 制冷技术 , 2024 , 44 ( 增刊1 ): 2 - 19 .
CHEN Huanxin , WANG Yiqing , ZHANG Li , et al . Development progress of data centers [J]. Chinese Journal of Refrigeration Technology , 2024 , 44 ( Suppl. 1 ): 2 - 19 .
孙西辉 , 刘旭 , 李宁 . 提升多联机空调能效的室外机换热器设计 [J]. 家电科技 , 2024 ( 5 ): 114 - 117 .
SUN Xihui , LIU Xu , LI Ning . Design of outdoor unit heat exchanger for variable refrigerant flow air conditioner to improve energy efficiency [J]. Journal of Appliance Science & Technology , 2024 ( 5 ): 114 - 117 .
何佳璇 , 张羽彤 , 管旭东 , 等 . 铝合金微通道换热器的腐蚀防护现状与进展 [J]. 中国腐蚀与防护学报 , 2024 , 44 ( 4 ): 993 - 1000 .
HE Jiaxuan , ZHANG Yutong , GUAN Xudong , et al . Present status and progress of corrosion protection for microchannel heat exchangers of Al-alloy [J]. Journal of Chinese Society for Corrosion and Protection , 2024 , 44 ( 4 ): 993 - 1000 .
章熙民 , 朱彤 , 安青松 , 等 . 传热学 [M]. 6版 . 北京 : 中国建筑工业出版社 , 2014 : 161 - 162 .
ZHANG Ximin , ZHU Tong , AN Qingsong , et al . Heat transfer [M]. 6th ed . Beijing : China Architecture & Building Press , 2014 : 161 - 162 .
KHODABANDEH R . Heat transfer in the evaporator of an advanced two-phase thermosyphon loop [J]. International Journal of Refrigeration , 2005 , 28 ( 2 ): 190 - 202 .
数据中心和通信机房用空气调节机组 : GB/T 19413—2024 [S]. 北京 : 中国标准出版社 , 2024 .
Air conditioning unit for data center and communication room : GB/T 19413—2024 [S]. Beijing : Standards Press of China , 2024 .
于传波 . 数据中心水冷背板系统的实验及模拟研究 [D]. 长沙 : 湖南大学 , 2023 .
YU Chuanbo . Experimental and simulation research on water-cooled backplane system in data center [D]. Changsha : Hunan University , 2023 .
赵晓 , 薛佳 , 刘占盛 , 等 . 自然冷源技术研究综述 [J]. 暖通空调 , 2023 , 53 ( 增刊2 ): 143 - 147 .
ZHAO Xiao , XUE Jia , LIU Zhansheng , et al . Review of natural cold source technology [J]. Journal of HV&AC , 2023 , 53 ( Suppl. 2 ): 143 - 147 .
严政 , 吴学渊 , 黄翔 , 等 . 水侧自然冷却技术在雄安城市计算中心的应用研究 [J]. 建筑科学 , 2023 , 39 ( 1 ): 93 - 100 .
YAN Zheng , WU Xueyuan , HUANG Xiang , et al . Application of water side natural cooling technology in Xiongan Urban Computing Center [J]. Building Science , 2023 , 39 ( 1 ): 93 - 100 .
张泉 , 熊磊 , 张荩文 . 数据中心水冷系统温排水对水环境影响研究 [J]. 建筑热能通风空调 , 2021 , 40 ( 1 ): 12 - 15 .
ZHANG Quan , XIONG Lei , ZHANG Jinwen . Investigation on influence of warm drainage from data center water cooling system on water environment [J]. Building Energy & Environment , 2021 , 40 ( 1 ): 12 - 15 .
王露 , 王馨翊 , 张博 , 等 . 高密度数据中心相变风辅液冷系统节能分析 [J/OL]. 清华大学学报(自然科学版) , 2025 : 1 - 8 . ( 2025-06-10 )[ 2025-06-30 ]. https://link.cnki.net/doi/10.16511/j.cnki.qhdxxb.2025.22.031 https://link.cnki.net/doi/10.16511/j.cnki.qhdxxb.2025.22.031 .
WANG Lu , WANG Xinyi , ZHANG Bo , et al . Energy efficiency analysis of phase-change air-assisted liquid cooling systems for high-density data centers [J/OL]. Journal of Tsinghua University (Science and Technology) , 2025 : 1 - 8 .( 2025-06-10 )[ 2025-06-30 ]. https://link.cnki.net/doi/10.16511/j.cnki.qhdxxb.2025.22.031 https://link.cnki.net/doi/10.16511/j.cnki.qhdxxb.2025.22.031 .
0
浏览量
584
下载量
0
CSCD
关联资源
相关文章
相关作者
相关机构
京公网安备11010802024621