浏览全部资源
扫码关注微信
天津商业大学 天津市制冷技术重点实验室 天津 300134
刘圣春,男,教授,天津商业大学机械工程学院,13920682426,E-mail:liushch@tjcu.edu.cn。研究方向:自然工质替代,制冷系统节能与优化。
收稿:2024-12-02,
修回:2024-12-13,
录用:2025-02-11,
纸质出版:2026-04-16
移动端阅览
代宝民,王祥军,刘圣春等.排气余热驱动的引射过冷CO2热泵系统性能分析[J].制冷学报,2026,47(02):35-42.
Dai Baomin Wang Xiangjun Liu Shengchun Wang Mingxuan Xie Shandong Li Chenzi Zhang Tong.Performance Analysis of Ejector Subcooling Transcritical CO2 Heat Pump System Driven by the Discharge Waste Heat[J].Journal of Refrigeration,2026,47(02):35-42.
代宝民,王祥军,刘圣春等.排气余热驱动的引射过冷CO2热泵系统性能分析[J].制冷学报,2026,47(02):35-42. DOI: 10.12465/issn.0253-4339.20241202001. CSTR: XXXXX.XX.XXX.20241202001.
Dai Baomin Wang Xiangjun Liu Shengchun Wang Mingxuan Xie Shandong Li Chenzi Zhang Tong.Performance Analysis of Ejector Subcooling Transcritical CO2 Heat Pump System Driven by the Discharge Waste Heat[J].Journal of Refrigeration,2026,47(02):35-42. DOI: 10.12465/issn.0253-4339.20241202001. CSTR: XXXXX.XX.XXX.20241202001.
为解决基本跨临界CO
2
空气源热泵系统(Base)应用于建筑空间供暖时节流损失大、性能下降的问题,提出压缩机排气余热驱动的引射过冷跨临界CO
2
空气源热泵系统(ESH)。对ESH系统采用4种不同工质时的热力学性能进行了优化和分析。选取了5个不同典型城市的住宅建筑作为应用情景,对其供暖季节性能系数(HSPF)进行了分析。结果表明:ESH系统的COP随排气压力的增大先增加后降低,存在最优排气压力。相较于Base系统,使用R1234ze(Z)的ESH系统的性能系数提升最显著,最高可提升20.64%。ESH系统的排气压力比Base系统最高可降低9.20%,㶲效率可提升7.13%~18.61%。ESH系统的HSPF比Base系统高9.68%~14.21%,在严寒地区使用时性能提升更为显著。
To resolve the issues of significant throttling loss and performance degradation of a baseline transcritical CO
2
air-source heat pump system (Base) for building space heating, an ejector subcooling transcritical CO
2
air-source heat pump system (ESH) driven by the waste heat of the compressor discharge gas is proposed in this paper. The thermodynamic performance of the ESH system was optimized and analyzed using four working fluids. Five typical cities were selected for comparison, and the heating season performance factor (HSPF) was analyzed. The results reveal that the coefficient of performance (COP) of the ESH system first increased and then decreased with the increase of discharge pressure, and a
n optimal discharge pressure exists. Compared with the Base system, the ESH system using R1234ze(Z) displayed the most remarkable improvement in COP (with the highest increase of 20.64%). The discharge pressure of the ESH system reduced by up to 9.20% compared with that of the Base system, and the exergy efficiency increased by 7.13%-18.61%. The HSPF of the ESH system was 9.68% to 14.21% higher than that of the Base system. The performance improvement was higher when it was used in severely cold regions.
中国人民共和国生态环境部 . 我国正式接受《〈关于消耗臭氧层物质的蒙特利尔议定书〉基加利修正案》 [EB/OL]. ( 2021-06-21 )[ 2024-11-25 ]. https://www.mee.gov.cn/ywdt/hjywnews/202106/t202 10621_841062.shtml https://www.mee.gov.cn/ywdt/hjywnews/202106/t20210621_841062.shtml .
Ministry of Ecology and Environment of the People's Republic of China . China officially accepts the Kigali Amendment to the Montreal Protocol on Substances that deplete the ozone layer [EB/OL]. ( 2021-06-21 )[ 2024-11-25 ]. https://www.mee.gov.cn/ywdt/hjywnews/202106/t20210621_841062.shtml https://www.mee.gov.cn/ywdt/hjywnews/202106/t20210621_841062.shtml .
DONG Liwei , TONG Huan , LIU Xuetao , et al . Comprehensive analysis of modified carbon dioxide heat pump systems and determination of operating schemes for residential heating: a multi-objective optimization approach [J]. Energy Conversion and Management , 2024 , 306 : 118272 .
ILLÁN-GÓMEZ F , GARCÍA-CASCALES J R , VELASCO F J S , et al . Numerical performance of a water source transcritical CO 2 heat pump with mechanical subcooling [J]. Applied Thermal Engineering , 2023 , 219 : 119639 .
SCHOENFIELD J , HWANG Y , RADERMACHER R . CO 2 transcritical vapor compression cycle with thermoelectric subcooler [J]. HVAC&R Research , 2012 , 18 ( 3 ): 297 - 311 .
DAI Baomin , YANG Haining , LIU Shengchun , et al . Hybrid solar energy and waste heat driving absorption subcooling supermarket CO 2 refrigeration system: energetic, carbon emission and economic evaluation in China [J]. Solar Energy , 2022 , 247 : 123 - 145 .
HUANG B J , PETRENKO V A , CHANG J M , et al . A combined-cycle refrigeration system using ejector-cooling cycle as the bottom cycle [J]. International Journal of Refrigeration , 2001 , 24 ( 5 ): 391 - 399 .
CHEN G , VOLOVYK O , ZHU D , et al . Theoretical analysis and optimization of a hybrid CO 2 transcritical mechanical compression-ejector cooling cycle [J]. International Journal of Refrigeration , 2017 , 74 : 86 - 94 .
IERIN V , CHEN G , VOLOVYK O , et al . Hybrid two-stage CO 2 transcritical mechanical compression-ejector cooling cycle: thermodynamic analysis and optimization [J]. International Journal of Refrigeration , 2021 , 132 : 45 - 55 .
KUMAR K , GUPTA H K , KUMAR P . Analysis of a hybrid transcritical CO 2 vapor compression and vapor ejector refrigeration system [J]. Applied Thermal Engineering , 2020 , 181 : 115945 .
YADAV V K , SARKAR J . Thermodynamic, economic, and environmental analyses of various novel ejector refrigeration subcooled transcritical CO 2 systems [J]. International Journal of Energy Research , 2021 , 45 ( 11 ): 16115 - 16133 .
CALM J , HOURAHAN G . Physical, safety, and environmental data for current and alternative refrigerants [C]// The 23th International Congress of Refrigeration . Prague, Czech Republi , 2011 .
DENG Jianqiang , JIANG Peixue , LU Tao , et al . Particular characteristics of transcritical CO 2 refrigeration cycle with an ejector [J]. Applied Thermal Engineering , 2007 , 27 ( 2/3 ): 381 - 388 .
DAI Yiping , WANG Jiangfeng , GAO Lin . Exergy analysis, parametric analysis and optimization for a novel combined power and ejector refrigeration cycle [J]. Applied Thermal Engineering , 2009 , 29 ( 10 ): 1983 - 1990 .
LIU F , GROLL E A . Study of ejector efficiencies in refrigeration cycles [J]. Applied Thermal Engineering , 2013 , 52 ( 2 ): 360 - 370 .
SARKAR J . Performance analyses of novel two-phase ejector enhanced multi-evaporator refrigeration systems [J]. Applied Thermal Engineering , 2017 , 110 : 1635 - 1642 .
BAI Tao , YAN Gang , YU Jianlin . Thermodynamic analyses on an ejector enhanced CO 2 transcritical heat pump cycle with vapor-injection [J]. International Journal of Refrigeration , 2015 , 58 : 22 - 34 .
GENG Lihong , LIU Huadong , WEI Xinli , et al . Energy and exergy analyses of a bi-evaporator compression/ejection refrigeration cycle [J]. Energy Conversion and Management , 2016 , 130 : 71 - 80 .
ROBINSON D M , GROLL E A . Efficiencies of transcritical CO 2 cycles with and without an expansion turbine [J]. International Journal of Refrigeration , 1998 , 21 ( 7 ): 577 - 589 .
CHEN Guangming , IERIN V , VOLOVYK O , et al . An improved cascade mechanical compression-ejector cooling cycle [J]. Energy , 2019 , 170 : 459 - 470 .
房间空气调节器能效限定值及能效等级 : GB 21455—2019 [S]. 北京 : 中国标准出版社 , 2019 .
Minimum allowable values of the energy efficiency and energy efficiency grades for room air conditioners : GB 21455—2019 [S]. Beijing : Standards Press of China , 2019 .