CHU JUNJIE, HUANG XIANG, SUN TIEZHU, et al. Experimental Study on the Performance of a Countercurrent Dew-point Indirect Evaporative Cooler. [J]. Journal of refrigeration, 2019, 40(1).
DOI:
CHU JUNJIE, HUANG XIANG, SUN TIEZHU, et al. Experimental Study on the Performance of a Countercurrent Dew-point Indirect Evaporative Cooler. [J]. Journal of refrigeration, 2019, 40(1). DOI: 10.3969/j.issn.0253-4339.2019.01.121.
Experimental Study on the Performance of a Countercurrent Dew-point Indirect Evaporative Cooler
A new countercurrent dew-point indirect evaporative cooler was developed
and its cooling performance was experimentally studied in this work. The wet-bulb efficiency
dew-point efficiency
and cooling capacity of the cooler were tested and analyzed under various working conditions simulating dry area
moderate-humidity area
and high-humidity area in an enthalpy-difference laboratory. The experimental results show that the wet-bulb efficiency reached 105.6% and the dew-point efficiency reached 76% under standard drying conditions (dry-bulb temperature 38 ℃ and wet-bulb temperature 23 ℃) and air-flow ratio of secondary air/primary air = 1.1. The cooling capacity was tested as 2.83 kW
and the dry-bulb temperature decrease of the cooler reached 15.2 ℃. By the experimental results simulating the working conditions of Urumqi and standard dry environment
the dew-point indirect evaporative cooling technology shows many advantages and broad application prospects in the hot and dry areas in northwestern China.
关键词
露点间接蒸发冷却实验工况冷却效率制冷量
Keywords
dew point indirect evaporative coolingtest conditionscooling efficiencyrefrigerating capacity
Simulation and Experimental Research on Performance of an Air Cooler with Liquid Feed Pump
Anti-condensation Characteristics of High Permeability Films for Radiation Air Conditioning in Typical Urban Indoor Environments of Different Climate Zones
Experimental Research of Heat Transfer Performance for Unsaturated Evaporative Cooler
Experimental Study of Dry-bulb and Wet-bulb Temperature Variations on Performance of Ducted Heat Pump
Related Author
Jin Lei
Deng Wenchuan
He Yongning
Cao Feng
Qian Hua
Chen Weijie
Zheng Xiaohong
Ma Jianchao
Related Institution
School of Energy and Power Engineering, Xi’an Jiaotong University
Wuxi Freshair AQ Technology Co., Ltd.
School of Energy and Environment, Southeast University