Study on the Multi-energy Complementary Absorption Heat Pump Applied for Combined Cooling and Heating with Large Temperature Zone
it is of great importance to realize low-carbon combined cooling and heating supply in distributed areas away from centralized cooling and heating network. In this paper
a combined cooling and heating system based on absorption heat pump is proposed
which uses a variety of clean and renewable energy such as solar heat
geothermal
waste heat
biomass and air-source energy to achieve the combined cooling and heating in a wide temperature zone of -20-100℃
suitable for distributed areas such as villages
cities and industrial parks. The system model is constructed based on Aspen
and a prototype is set up. The prototype uses vacuum tube collector to capture solar thermal energy
and introduces natural gas secondary combustion to balance load fluctuations of solar energy. Through the medium circulation and valve switching
multiple sets of indoor heating/cooling ends can be driven by a single set of absorption heat pump and outdoor unit. Environmental test of the prototype was performed in Jinan
and during the whole testing period the solar thermal ratio could reach 35%. Through gas proportional regulation
all-weather stable energy supply was achieved. Moreover
a wide range of concentration adjusting was realized by level control of solution tank
so that the system can operate efficiently in a wider temperature zone. It was found that the COP of cooling reached 0.30-0.43 at -20℃
and 0.70-0.78 at 7℃
with cooling water temperatures varies from 30 to 20℃; and the COP of heating reached 1.40-1.90 at 45℃
and 1.35-1.56 at 80℃
with evaporation temperature varies from -15 to 20℃. It was showed that by introducing solar thermal driving and ambient energy recovery
the proportion of renewable energy of the system was over 50%. Compared with the traditional method of gas furnace plus air conditioning
the annual operating cost and carbon emission of the proposed system was reduced by over 54.3% and 44%