Cite this article
  •    [Click To Copy]
  •    [Click To Copy]
【Print This Page】 【Download PDF Full Text】 View/Add CommentDownload reader Close

←Previous Article|Next Article→

Back Issue    Advanced Search

This Article Has Been:Browse 1698 Times   Download 1741 Times QR code information in this article
Scan Up The Code!
板式蒸发冷却空冷器的阻力和传热特性实验研究
李春光, 张旭, 黄晓庆, 田震
0
(同济大学暖通空调与燃气研究所)
摘要:
通过改变风量、水量和增湿供水量,对板式蒸发空冷器阻力及传热特性进行实验研究,得到干工况下空气侧和热水侧的阻力及对流换热系数关联式。实验结果表明,增湿工况下,空气侧阻力几乎不受影响,换热系数随增湿供水量增加而增大,约为干工况时的6倍。
关键词:  喷雾增湿  空冷器  阻力  传热系数
DOI:
Received:March 22, 2012
基金项目:国家“十二五”科技支撑计划(2011BAJ08B09)资助项目
Experimental Study on Resistance and Heat Transfer Characteristics of Plate Evaporative Air Cooler
Li Chunguang, Zhang Xu, Huang Xiaoqing, Tian Zhen
(HVAC and Gas Institute, Tongji University)
Abstract:
The resistance and heat transfer characteristics of a plate evaporative air cooler are investigated experimentally through varying the flow rate of air, hot water and humidification water. Correlations for the air side and hot water side pressure drop and convection heat transfer coefficient are obtained. The results of experiment show that the pressure drop of air side is not affected by humidification water. The heat transfer coefficient increases with the increase of humidification water flow rate and it is about 5 times larger than the one under dry condition.
Key words:  spray humidification  air cooler  pressure drop  heat transfer coefficient

用微信扫一扫