并联型调温除湿机制冷剂流量三通比例调节阀动作特性的实验研究
崔建宁,韩旭,贾永杰,周森林
0
(江苏省经贸职业技术学院;解放军理工大学工程兵工程学院;南京天加空调公司)
摘要:
地下工程的大量涌现,使得节能效果好、效率高的并联型调温除湿机得到了广泛的应用,三通比例调节阀是并联型调温除湿机的关键部件,其动作特性对机组性能具有重要影响。在构建双冷凝器并联型调温除湿系统的基础上,测试了制冷剂流量三通比例调节阀开度变化对机组性能的影响, 结果表明:1)可以通过调节三通比例调节阀的开度实现送风温度的连续调节,三通阀作用区域为开度30%~80%;2)三通阀开度变化对系统除湿量有影响。阀门开度在50%~65%时,系统除湿量最大,输入功率最小,具有最高的单位功率除湿量;3)通过调节阀门开度,可以实现制冷剂流量的调节,制冷剂流量最大值出现在阀门开度为50%~70%区间内。这些调节方法对提高并联型调温除湿机效率具有一定意义。
关键词:  热工学  调温除湿机  制冷剂流量  三通比例调节阀
DOI:
    
基金项目:
Experiments Study on Movements Characteristics of Three-way Modulating Control Valve of the Parallel Condensers Dehumidifier
Cui Jianning,Han Xu,Jia Yongjie,Zhou Senlin
(Jiangsu Economic & Trade Polytechnic;Engineering Institute of Crops of Engineers, PLA Univ. of Sci.;TICA air-conditioning company)
Abstract:
With the rapid growth of underground projects, the temperature control dehumidifier with parallel condensers has been widely used for its energy saving and high efficiency. The influence of the 3-way modulating control valve in temperature control dehumidifier with parallel condensers on unit cooling, dehumidifying and supply air temperature was studied, The result shows that: (1) the continuous temperature adjustment could be achieved by adjusting the opening degree of the three-way valve. The effective region of the three-way valve was between 30% and 80%; (2) the opening degree of the three-way valve has influence on the dehumidification of the unit; when the open degree is between 50% and 65%, the unit has the lowest value in input power and highest value in dehumidification; (3) the refrigerant’s flow rate could be modulated by modulating the opening degree of the 3-way valve, and the highest flow appeared when the opening degree is between 50% and 70%. The ways of adjustment are very useful for improving the efficiency of temperature control dehumidifier with parallel condensers.
Key words:  Pyrology  Temperature control dehumidifier  The flow rate of refrigerant  Three-way modulating control valve