Xu Peng, Mu Xin. Experimental Study on Internal Heat and Humidity Parameters of Regenerative Indirect Evaporative Cooler[J]. Journal of Refrigeration, 2023, 44(4): 133-140.
DOI:
Xu Peng, Mu Xin. Experimental Study on Internal Heat and Humidity Parameters of Regenerative Indirect Evaporative Cooler[J]. Journal of Refrigeration, 2023, 44(4): 133-140.DOI: 10.3969/j.issn.0253-4339.2023.04.133.
Experimental Study on Internal Heat and Humidity Parameters of Regenerative Indirect Evaporative Cooler
Based on a self-built indirect evaporative cooler experimental prototype
high-precision temperature and humidity sensors were placed inside a narrow airflow channel for dynamic data acquisition. An enthalpy difference chamber was used to create a stable external environment and hence inlet parameters for the channel. The influence of different inlet air velocities
primary to secondary air ratios
and environmental heat and humidity parameters on the heat and humidity exchange process of the airflow inside the channel was studied. The results showed that the relative humidity of the secondary air changed rapidly. When the relative humidity exceeds 95%
the evaporation process is saturated. A wet-channel length of 40 cm satisfies the design requirements of most evaporative coolers. At low air velocity and primary to secondary air ratios
the saturation evaporation length of the evaporative cooler was shorter
while the cooling capacity was higher. For the standard initial conditions of dry bulb temperature 37.8 °C and wet bulb temperature 21.1 °C
the channel air velocity was constant at 0.5 m/s
and the relative humidity rose to 95.7% after an evaporation distance of 10 cm. The relative humidity of the ambient air had a significant impact on the cooling performance. Under the same dry bulb temperature of 33.5 °C
the average temperature of the secondary air in Urumqi with a wet bulb temperature of 18.2 °C is 7 °C lower than that in Beijing with a wet bulb temperature of 26.4 °C.
Development and Experimental Validation of an Integrated Evaporative and Hybrid Air-Liquid Cooling System for Intelligent Computing Centers
Study on Structural Optimization and Thermal Management Performance of Embedded Composite Cooling Plate Based on Wavy Channel
Fabrication of Transparent Superhydrophobic Surface and lts Anti-Frosting Performance
Correction of Heat Transfer and Mass Transfer Model Parameters for Peaches in Refrigerated Storage
Research Status and Prospects of Terminals of Central Air-Conditioning Systems
Related Author
Gao Yuan Huang Xiang Feng Shihao Chu Junjie
黄翔
冯世豪
褚俊杰
Cai Yunxiang
Sun Qin
Zhang Bobo
Gu Xiaobin
Related Institution
School of Urban Planning and Municipal Engineering, Xi'an Polytechnic University
Guangdong Provincial Key Laboratory of Renewable Energy, Guangzhou Institute of Energy Conversion, Chinese Academy of Sciences
School of Energy Science and Technology, University of Science and Technology of China
Key Laboratory of Enhanced Heat Transfer and Energy Conservation,Ministry of Education , Department of New Energy Science and Engineering,Beijing University of Technology
School of Mechanical Engineering, Tianjin University of Commerce