摘要: |
本文针对地下工程的特点,提出了一种适用于其空调系统能效评价的指标——运行需求能效比,并给出其明确定义和计算方法。并建立了空调系统从整体到局部的能效评价策略,给出各子系统的能效参考限值。选取夏热冬冷地区某小型地下工程为实例,进行空调系统的能效评价,结果表明:该系统在日常维护期处于较低的能效水平,根据评价结果对原工程进行改造,改造后系统总能效提高了18.9%,验证了该评价方法的可行性和合理性。 |
关键词: 防护工程 运行需求能效比 运行工况 空气调节系统 热负荷 除湿 |
DOI: |
投稿时间:2017-11-24 修订日期:2018-02-09
|
基金项目:Evaluation Method for Air-conditioning System in Protective Engineering |
|
Evaluated Method for Air-conditioning System in Protective Engineering |
Sheng Jun, Miao Xiaoping, Wei Huan, Wei Zijie, Shao Guangming
|
(School of Defense Engineering, Army Engineering University of PLA) |
Abstract: |
According to the features of protective engineering, an index for energy efficiency evaluation of an air-conditioning system is proposed, which is named as operating-demand energy efficiency ratio. Its definition and calculation method are provided in this paper. The energy efficiency evaluation strategy of an air-conditioning system is established from the whole system and its components, and the limiting values of the energy efficiency are provided. By taking a small underground engineering in hot summer and cold winter zones as an example, the energy efficiency evaluation of the air-conditioning system was carried out. The evaluation result shows that the system exhibited a daily low level of energy efficiency. On the basis of the result, the original project was retrofitted, and the energy efficiency of the system was improved by 18.9%, which verifies the feasibility and rationale of the proposed evaluation method. |
Key words: protective engineering operation demand energy efficiency ratio operating conditions air-conditioning system heat load dehumidification |