Liu Yijun, Ma Zhirong, Chen Meng, et al. Influence of Floor Air Supply Methods and Impact of Geometric Parameters on the Thermal Performance of Data Centers[J]. Journal of refrigeration, 2023, 44(1).
DOI:
Liu Yijun, Ma Zhirong, Chen Meng, et al. Influence of Floor Air Supply Methods and Impact of Geometric Parameters on the Thermal Performance of Data Centers[J]. Journal of refrigeration, 2023, 44(1). DOI: 10.3969/j.issn.0253-4339.2023.01.071.
Influence of Floor Air Supply Methods and Impact of Geometric Parameters on the Thermal Performance of Data Centers
The indoor thermal environment of data centers is based on the supply airflow distribution
which is significantly affected by the geometric configuration of the air-supply system. This study compares four commonly used air supply layouts
namely the cold/hot-aisle airflow open-ended system
hot aisle containment system
cold aisle under racks system
and cold aisle containment system. For each air supply layout
geometric factors such as the plenum height
perforation rate
baffle position
and baffle angles were investigated. Using ANSYS Fluent
up to 288 models of CRAC with different air supply modes and configurations were built. The models were validated using the temperature measurement data at the SmartAisle? cold aisle containment system. The average rack and hot spot temperatures
thermal performance evaluation index
and return temperature index were used as the metrics for comparison. The results show that both increasing the plenum height and decreasing the perforation rate within a certain range contribute to thermal performance improvement. Considering the room temperature profile and evaluation metrics
the overall best performance is achieved in the cold aisle containment case. Finally
the effects of various factors when using \/-shaped and /\-shaped baffles were compared using the models of the cold aisle containment system. The results show that when using \/-shaped and /\-shaped baffles
the optimal perforation rate is 20%
while the optimal static pressure height is 0.5 m and 0.6 m
respectively. Overall
\/-shaped baffles achieve better temperature uniformity than /\-shaped baffles.