This study proposes a "one tower with three functions" solution for a dehumidification type frost-free air-source heat pump (ASHP) system
which can not only solve the frost problem of traditional ASHP systems in winter
but also improve the performance of the units in summer. The effects of air temperature
humidity
mass flow rate
solution temperature
and mass concentration were studied under dehumidification conditions. Additionally
solution mass concentration
the effect of solution temperature under regenerative conditions on the air exergy of the inlet and outlet
dehumidification/regenerative exergy
system input
output exergy
and exergy efficiency were studied by constructing the test bench. The results show that under dehumidification
there is an increase in the dehumidification exergy with an increase in the air temperature
air mass flow rate
and solution mass flow rate
and a decrease in the air humidity
solution temperature
and solution mass concentration. Additionally
there is an increase in the system exergy efficiency with an increase in the air temperature
humidity
air mass flow rate
mass flow rate and mass concentration of the solution
and a decrease in the solution temperature
air humidity and mass concentration of the solution. These have an insignificant effect on the exergy efficiency when the efficiency is up to 0.201. Under regenerative conditions
there is an increase in the regeneration exergy with an increase in the solution mass concentration and solution temperature. There is also an increase in the system exergy efficiency with an increase in the solution mass concentration
and a decrease in the solution temperature. The solution temperature has an insignificant effect on the exergy efficiency
when the efficiency is up to 0.1088. The efficiency of this system is higher than that of a conventional ASHP system under experimental conditions.