Huang Chen, Li Jialin, Zhang Yalin, et al. Study on Vertical Temperature Profiles of Stratified Air Conditioning with Low-sidewall Air Supply in Large Space Buildings[J]. Journal of refrigeration, 2020, 41(2).
DOI:
Huang Chen, Li Jialin, Zhang Yalin, et al. Study on Vertical Temperature Profiles of Stratified Air Conditioning with Low-sidewall Air Supply in Large Space Buildings[J]. Journal of refrigeration, 2020, 41(2). DOI: 10.3969/j.issn.0253-4339.2020.02.136.
Study on Vertical Temperature Profiles of Stratified Air Conditioning with Low-sidewall Air Supply in Large Space Buildings
A multi-node model was developed to predict the vertical temperature profiles of a stratified air-conditioning system in a certain large space building with low-sidewall air supply and return. Then experiments were carried out in the building under 5 working conditions with a different air volume (1.5×104–2.5×104 m3/h) and outdoor meteorological parameters (28-34 ℃). The results show that the maximum relative errors of the calculated values of each condition are 6%
7%
14%
-6%
and 15%
respectively
and the average standard deviation of each condition is 2.05 ℃
which validated the multi-node model. Afterwards
the multi-node model was used to analyze the characteristics of the thermal environment of stratified air-conditioning system in large space buildings with low-sidewall air supply and return by changing air volume
outdoor air temperature
and solar radiation. Finally a graph is drawn to guide the adjustment of air volume as indoor and outdoor environmental parameters changes.