Thermodynamic Performance Analysis of a Triple-loop Air-source Heat-pump Heat Recovery System
To improve the performance of an air-source heat pump system under large temperature difference conditions
this paper proposed a triple-loop air-source heat pump system scheme. An energy recovery performance test platform was set up according to the exhaust energy recovery in a public building air-conditioning system. The performances of the single- and triple-loop heat-pump systems were tested through experiments under different outdoor-temperature conditions in winter and summer. The results show that the overall performance of the triple-loop system was significantly higher than that of the single-loop system under all operating conditions. With the increase in the indoor and outdoor temperature difference
the triple-loop heat pump system could significantly minimize the problems of excessive compression ratio and system performance degradation of the traditional air-source heat pump. Under winter conditions
the increase rate of the coefficient of performance (COP) of the triple-loop system reached up to 1.88. When the indoor and outdoor temperature difference was 40 ℃
the COP of the triple-loop system was 54.8% higher than that of the single-loop system. Under summer conditions
the increase rate of the COP of the triple-loop system reached 89.8%. When the indoor and outdoor temperature difference was 13 ℃
the COP of the triple-loop system was 74.6% higher than that of the single-loop system.
Experimental Study on Effect of Fin Structure on Frosting Characteristics of Finned Tube Heat Exchangers
Research Status and Prospect on Defrosting Control Method of Air Source Heat Pump
Experimental Research on Performance of Cascade Heat Pump with Variable Rotation Speed of High-temperature Compressor
Analysis of Frosting Characteristics of Air Source Heat Pumps in Winter Based on Actual Operation Data
Related Author
Xie Fulin
Guo Xianmin
Guo Xinwei
Xue Jie
Wang Fenghao
Ma Longxia
Wang Zhihua
Lou Yechun
Related Institution
Tianjin Key Laboratory of Refrigeration Technology,Tianjin University of Commerce
ZVISION Technologies Co.,Ltd
School of Human Settlement Environment and Architectural Engineering, Xi'an Jiaotong University
Building Energy Conservation Research Center, Xi'an Jiaotong University
Tianjin University of Commerce, Refrigeration Engineering Research Center of Ministry of Education of People’s Republic of China, Tianjin Key Laboratory of Refrigeration Technology, Tianjin Refrigeration Engineering Technology Center