Qin Huanghui. Experimental Study on Variable-frequency Screw Compressor with Economizer under Variable Working Conditions[J]. Journal of refrigeration, 2018, 39(4).
DOI:
Qin Huanghui. Experimental Study on Variable-frequency Screw Compressor with Economizer under Variable Working Conditions[J]. Journal of refrigeration, 2018, 39(4). DOI: 10.3969/j.issn.0253-4339.2018.04.123.
Experimental Study on Variable-frequency Screw Compressor with Economizer under Variable Working Conditions
To improve the efficiency of a variable-frequency screw compressor with an economizer
the effect of parameters such as the discharge pressure of the compressor
motor frequency
injection pressure of the economizer
and volumetric efficiency on the efficiency of compressor were studied experiementally
and the injection pressure change rule of the economizer was obtained by changing the discharge pressure of the compressor or the motor frequency. Under the condition of a condensing temperature of 40 ℃ and evaporating temperature of 5 ℃
the economizer injection pressure rises by 88.3 kPa with the motor frequency changing from 200 Hz to 50 Hz
and only by 4.9 kPa when the discharge pressure was increased by 30%
which resulted in a 2% drop in volumetric efficiency of the compressor. The result shows that motor frequency has a greater effect on the injection pressure and volumetric efficiency compared to the discharge pressure of the compressor.