Feasibility Study on Entransy Analysis Applied in the Operation Optimization of Air Conditioning Systems
To optimize the operation of air conditioning systems
the extremum entransy increase principle is proposed
and an entransy loss model for each component and entransy increase model for the whole system are established for air conditioning systems based on entransy theory. The entransy increase rate of the air conditioning system under different operation conditions is experimentally studied when the system cooling load and total power consumption are fixed separately. The results prove that the extremum entransy increase principle holds and determine the optimal operation conditions. When the system cooling load is 5 kW
the optimal compressor frequency is 70 Hz
optimal chilled water flow rate is 0.6 kg/s
and optimal cooling water flow rate is 0.9 kg/s. These parameter values produce the minimum system entransy increase rate
minimum power consumption rate
and maximum system efficiency. When the system power consumption is 2.8 kW
the optimal compressor frequency
chilled water flow rate
and cooling water flow rate are 97.9 Hz
0.41 kg/s
and 1.00 kg/s
leading to the maximum system entransy increase rate