Experimental Investigation on Thermal Performance of Desiccant Coated Heat Exchanger in Series with Heat Exchanger
A desiccant coated heat exchanger can handle sensible load and latent load simultaneously; however
owing to the influence of adsorption heat
the heat load and moisture load treatment is not synchronous
and the ability to handle sensible load is insufficient. Based on this
another sensible heat exchanger is added in-series for the air secondary treatment. An experiment setup was built to test the dynamic performance of two heat exchangers connected in-series. In addition
the influence of the main operation parameters including the water temperature
air temperature
air humidity
and air velocity on the system performance are analyzed. The results show that a sensible heat exchanger can clearly improve the ability to handle sensible load
particularly during the beginning period
and the cooling capacity of the system is also significantly improved. Moreover
under the experiment conditions
the cooling and heating water temperatures can both improve the cooling capacity and COP
a higher air temperature and relative humidity ratio lead to a better performance
and a lower air velocity is helpful for increasing the average dehumidification capacity and the effective dehumidification time.