Exergy Analysis of Double Cooling Source Refrigerating Unit Based on Large Temperature Glide Zeotropic Mixture
To study the influence of the temperature of chilled water on the exergy loss of the double cooling source refrigerating unit
the model of exergy analysis on the unit that adopts the large temperature glide zeotropic mixture R32/R236fa (60%/40%) as refrigerant is established
and the experimental platform of the double cooling source refrigerating unit was set up for experimental exergy analysis in this paper. The theoretical exergy loss and the experimental exergy loss of the refrigeration unit are studied when the condensation temperature is 32 ℃ and the temperature of chilled water is 18 ℃/8 ℃
17 ℃/6 ℃
and so on respectively. The results show that the minimum exergy destruction occurs when the inlet water temperature of the condenser is 32 ℃
higher and lower outlet water temperatures of the evaporator are 8 ℃ and 17 ℃. At the same time