Experimental Investigation on a Pump-driven Two Phase Cooling Unit and Its Energy Saving Effect
Compared with the traditional vapor compression air conditioner
the pump-driven two phase cooling unit has a great potential in energy saving of data centers for it consumes less power and has a higher energy efficiency ratio when air temperature is low. However
insufficient control strategies not only hinder the improvement of performance
but also influence the accuracy of indoor temperature controlling
which limits the practical application. For a better application on small data centers
this paper designs a control system for the pump-driven two phase cooling unit
and studies its operating performance using in a small data center. This paper also fits the operating characteristic curves and makes an energy saving analysis. The results show that when the set point of indoor temperature is 22 ℃
the pump-driven system can fit the heat load well and get a good energy saving effect under the condition of an outdoor temperature of 10 ℃ or lower
and it can achieve at least a ratio of 26.77% on energy saving comparing with the existing air conditioner of the data center.