The Experimental Research on Refrigerant Mixtures of a Linde-Hampson Refrigeration System
The performance of quaternionic refrigerant mixtures
R345fa/R600a/R508b/R14
in Linde-Hampson refrigeration cycle was experimentally investigated. To get the lowest operation temperature
the components of refrigerant mixtures were optimized. The influence of ambient temperature on system operational performance was analyzed. It is shown that the lowest system operation temperature could reach from -45℃ to -85℃ when mixing the four refrigerant components at different species ratio
. If the proportion of the refrigerant mixtures charged is R245fa:R600a:R508b:R14=0.45:0.3:0.18:0.07
the operating temperature of the system can reach -85℃ when the ambient temperature is 35℃. With the same refrigerant mixtures
the system temperature can reach -89.3℃ if the ambient temperature decreases from 35℃ to 5℃.