Experimental Study on Effect of Clearance Volume on Performance of Rotary Compressor[J]. Journal of Refrigeration, 2006, 27(6): 22-24.
DOI:
Experimental Study on Effect of Clearance Volume on Performance of Rotary Compressor[J]. Journal of Refrigeration, 2006, 27(6): 22-24. DOI: 10.3969/j.issn.0253-4339.2006.06.005.
Experimental Study on Effect of Clearance Volume on Performance of Rotary Compressor
On the basis of analyzing the effects of clearance volume on the performance of a rotary compressor
the clearance volume of the rotary compressor was reduced and the modified rotary compressor was tested.The experimental results show that the clearance volume has effect on the performance of the rotary compressor and the performance is improved when the clearance volume decreases.Compared with the original compressor
the refrigerating capacity and COP of the modified compressor increase by about 2.43% and 3.23%
respectively.However
the noise of the modified rotary compressor rises
but its value is still less than national standards requirement(66 dB).