浏览全部资源
扫码关注微信
1.西南科技大学土木工程与建筑学院 绵阳 621010
2. 成都巨量引擎信息技术有限公司 成都 610095
Chun Liang, male, Ph. D., associate professor,School of Civil Engineering and Architecture,Southwest University of Science and Technology. 86-18846168573, E-mail: chunliang@swust.edu.cn. Research fields: evaporative cooling, vacuum membrane dehumidification, and building energy efficiency.
Received:03 August 2026,
Revised:2026-08-08,
Accepted:24 September 2026,
Online First:19 October 2026,
移动端阅览
聂大力,淳良,王顺森. 电储能露点蒸发冷却复合新风系统性能研究[J]. 制冷学报,XXXX,XX(XX):1-8.
Nie Dali,Chun Liang,Wang Shunsen. Performance of a Hybrid Fresh-Air System with Dew-Point Evaporative Cooling and Battery Energy Storage[J]. Journal of Refrigeration,XXXX,XX(XX):1-8.
聂大力,淳良,王顺森. 电储能露点蒸发冷却复合新风系统性能研究[J]. 制冷学报,XXXX,XX(XX):1-8. DOI: 10.12465/issn.0253-4339.20260803001.
Nie Dali,Chun Liang,Wang Shunsen. Performance of a Hybrid Fresh-Air System with Dew-Point Evaporative Cooling and Battery Energy Storage[J]. Journal of Refrigeration,XXXX,XX(XX):1-8. DOI: 10.12465/issn.0253-4339.20260803001.
为评价成都湿润夏季电储能露点蒸发冷却复合新风系统的运行性能,对成都市某办公建筑开展现场测试。依据功率、风速、运行时间和空气状态变化筛得11个工作日6 589个稳定数据点。结果表明:露点蒸发冷却器使新风温度由29.60 ℃降至23.03 ℃,露点效率和湿球效率分别为71.06%和100.34%;蒸发冷却段与机械制冷段焓降分别为3.20 kJ/kg和27.39 kJ/kg,预冷负荷分担率为(10.39±3.31)%,当该值大于9.81%时,系统性能系数(COP)相对变化率为正;系统日均COP为3.16~3.49,预冷耦合系统COP相对变化率为(0.82±4.17)%。30 kW·h储能单元日均可配对移峰11.70 kW·h,理论收益为4.59~5.74元/工作日。蒸发冷却段主要承担显热预冷,机械制冷段负责主体焓负荷和除湿;随室外空气状态调节蒸发冷却段运行,可提高系统工况适应性。
A field test was conducted in an office building in Chengdu to evaluate the performance of a fresh-air system integrating electrical energy storage, dew-point evaporative cooling, and mechanical refrigeration under humid summer conditions. A total of 6 589 stable data points over 11 working days were selected based on power, air velocity, operating duration, and air-state variations. The dew-point evaporative cooler reduced the fresh-air temperature from 29.60 ℃ to 23.03 ℃, corresponding to dew-point and wet-bulb effectiveness values of 71.06% and 100.34%, respectively. The enthalpy differences across the evaporative cooling and mechanical cooling sections were 3.20 and 27.39 kJ/kg, respectively. The precooling load fraction was (10.39 ± 3.31)%, and the system coefficient of performance (COP) increased when this ratio exceeded 9.81%. The daily mean COP ranged from 3.16 to 3.49, while its variation after precooling coupling was (0.82 ± 4.17)%. The 30 kW·h battery energy storage unit shifted 11.70 kW·h of load per day, yielding estimated savings of 4.59-5.74 CNY. The evaporative cooling section primarily provided sensible precooling, whereas mechanical refrigeration handled most of the enthalpy load and dehumidification. Adjusting the operation of the evaporative cooling section based on outdoor air conditions can enhance the system's adaptability to operating conditions.
International Energy Agency . Global energy review 2026 [R]. Paris : IEA , 2026
Programme United Nations Environment . Global cooling watch 2025: the free degrees [M]. Nairobi : UNEP , 2025 .
成家豪 , 张春路 . 住宅用排风热回收新风机组的能效评价 [J]. 制冷学报 , 2025 , 46 ( 5 ): 124 - 132 .
CHENG Jiahao , ZHANG Chunlu . Energy efficiency evaluation of residential fresh air units with exhaust air heat recovery [J]. Journal of Refrigeration , 2025 , 46 ( 5 ): 124 - 132 .
Lai Lanbo , Wang Xiaolin , Hu E , et al . A vision of dew point evaporative cooling: opportunities and challenges [J]. Applied Thermal Engineering , 2024 , 244 : 122683 .
Urso A , Velasco-Gómez E , Tejero-González A , et al . Experimental study of the optimal design and performance of a mixed-flow dew-point indirect evaporative cooler [J]. Applied Thermal Engineering , 2024 , 257 : 124294 .
Büker M S , Onay A E , Ertan A . Experimental performance evaluation of a novel indirect evaporative cooler with optimized heat exchanger design [J]. Applied Thermal Engineering , 2025 , 279 : 128072 .
Alam M S , Bin Mohd Zubir M N , Bin Muhamad M R , et al . A technological review of dew point evaporative cooling: experimental, analytical, numerical and optimization perspectives [J]. Journal of Building Engineering , 2024 , 91 : 109544 .
Chen Z , Zhao W J , Wang B C , et al . A first-of-its-kind two-stage dew-point evaporative cooler with high energy efficiency and compact design [J]. Energy Conversion and Management , 2025 , 341 : 120090 .
Li Xianli , Chang Yao , Liu Wenqiang , et al . Energy-saving potential of dew point indirect evaporative cooler applied in school building [J]. Applied Thermal Engineering , 2025 , 275 : 126865 .
Zaki A M , Bargal M H S , Antar M A , et al . Advances in indirect evaporative cooling: principles, integrated cycles, economic insights, and environmental implications [J]. Thermal Science and Engineering Progress , 2025 , 67 : 104078 .
Zhu Guangya , Wen Tao , Wang Qunwei , et al . A review of dew-point evaporative cooling: recent advances and future development [J]. Applied Energy , 2022 , 312 : 118785 .
Xiao Xin , Liu Jinjin . A state-of-art review of dew point evaporative cooling technology and integrated applications [J]. Renewable and Sustainable Energy Reviews , 2024 , 191 : 114142 .
Chen Qian , Ja M K , Burhan M , et al . A hybrid indirect evaporative cooling-mechanical vapor compression process for energy-efficient air conditioning [J]. Energy Conversion and Management , 2021 , 248 : 114798 .
Chun Liang , Gong Guangcai , Peng Pei , et al . Research on thermodynamic performance of a novel building cooling system integrating dew point evaporative cooling, air-carrying energy radiant air conditioning and vacuum membrane-based dehumidification (DAV-cooling system) [J]. Energy Conversion and Management , 2021 , 245 : 114551 .
Mumtaz M , Pamintuan B C , Fix A J , et al . Hybrid membrane dehumidification and dewpoint evaporative cooling for sustainable air conditioning [J]. Energy Conversion and Management , 2023 , 294 : 117547 .
Delfani S , Esmaeelian J , Pasdarshahri H , et al . Energy saving potential of an indirect evaporative cooler as a pre-cooling unit for mechanical cooling systems in Iran [J]. Energy and Buildings , 2010 , 42 ( 11 ): 2169 - 2176 .
贺红霞 , 黄翔 , 何华明 , 等 . 数据中心用露点间接蒸发冷却与机械制冷复合空调的实验研究 [J]. 制冷学报 , 2020 , 41 ( 6 ): 71 - 76 .
He Hongxia , Huang Xiang , He Huaming , et al . Experimental investigation on dew point indirect evaporative cooling system combined with mechanical refrigeration for data center [J]. Journal of Refrigeration , 2020 , 41 ( 6 ): 71 - 76 .
Shakir A , Zhang Jingbang , He Yigang , et al . Coordinated optimization of household air conditioning and battery energy storage systems: implementation and performance evaluation [J]. Processes , 2025 , 13 ( 3 ): 631 .
Guide to the expression of uncertainty in measurement—Part 1: introduction : JCGM GUM-1:2023 [S].
四川省发展和改革委员会 . 关于进一步调整我省分时电价机制的通知: 川发改价格 〔2025〕 185 号[EB/OL]. ( 2025-04-30 )[ 2026-07-28 ]. https://fgw.sc.gov.cn/sfgw/qtwj/2025/4/30/8f5b20c4de7e4df48faa04935e512111.shtml https://fgw.sc.gov.cn/sfgw/qtwj/2025/4/30/8f5b20c4de7e4df48faa04935e512111.shtml .
Sichuan Provincial Development and Reform Commission . Notice on further adjusting the time-of-use electricity pricing mechanism in Sichuan Province: Sichuan DRC Pricing 〔2025〕No.185[EB/OL]. ( 2025-04-30 )[ 2026-07-28 ]. https://fgw.sc.gov.cn/sfgw/qtwj/2025/4/30/8f5b20 c4de7e4df48faa04935e512111.shtml https://fgw.sc.gov.cn/sfgw/qtwj/2025/4/30/8f5b20c4de7e4df48faa04935e512111.shtml .
四川省水电投资经营集团有限公司代理购电价格公告 [EB/OL]. ( 2026-06-28 )[ 2026-07-28 ]. https://www.scsdjt.com/Public/Upload/file/2026/0708/20260708123228315.pdf https://www.scsdjt.com/Public/Upload/file/2026/0708/20260708123228315.pdf .
Electricity purchasing agency price announcement of Sichuan Hydropower Investment and Management Group Co. , Ltd . [EB/OL]. ( 2026-06-28 )[ 2026-07-28 ]. https://www.scsdjt.com/Public/Upload/file/2026/0708/202607081 23228315.pdf https://www.scsdjt.com/Public/Upload/file/2026/0708/20260708123228315.pdf .